Experiments were conducted to study the condensation heat transfer characteristics of horizontal enhanced tubes. In the current experiment, six different enhanced tubes, including 26, 40 fpi low fin tubes and four three-dimensional-fin tubes, were tested. The working fluid used in the experiment was HCFC-22. Data were presented in the form of overall heat transfer coefficient at three working pressures, namely 1.32, 1.47 and 1.62 Mpa. In addition, the condensing heat transfer coefficients for the test tubes were obtained from the Wilson plot technique.
CITATION STYLE
Cheng, W. Y., Wang, C. C., Hu, Y. Z. R., & Huang, L. W. (1996). Film condensation of HCFC-22 on horizontal enhanced tubes. International Communications in Heat and Mass Transfer, 23(1), 79–90. https://doi.org/10.1016/0735-1933(95)00086-0