Impact of Offshore Wind Power Integrated by VSC-HVDC on Power Angle Stability of Power Systems

0Citations
Citations of this article
5Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

Offshore wind farm connected to grid by VSC-HVDC loses frequency support for power system, so adding frequency control in wind farm and VSC-HVDC system is an effective measure, but it will change wind farm VSC-HVDC's transient stability on power system. Through theoretical analysis, concluding the relationship between equivalent mechanical power and electromagnetic power of two-machine system with the active power of wind farm VSC-HVDC, then analyzing the impact of wind farm VSC-HVDC with or without frequency control and different frequency control parameters on angle stability of synchronous machine by EEAC. The validity of theoretical analysis has been demonstrated through simulation in PSCAD/EMTDC.

Cite

CITATION STYLE

APA

Lu, H., & Tang, X. (2017). Impact of Offshore Wind Power Integrated by VSC-HVDC on Power Angle Stability of Power Systems. In IOP Conference Series: Materials Science and Engineering (Vol. 199). Institute of Physics Publishing. https://doi.org/10.1088/1757-899X/199/1/012003