An Improved Zonal Ventilation Control Method of Waiting Hall of High-Speed Railway Station Based on Real-Time Occupancy

4Citations
Citations of this article
6Readers
Mendeley users who have this article in their library.
Get full text

Abstract

The random movement of occupants in a high-speed railway station results in a more complex indoor environment. In this study, the indoor thermal environment and the thermal comfort in summer were investigated via field measurements and questionnaires in the waiting hall of a high-speed railway station. The results showed that there was an uneven horizontal temperature distribution in the area, and over 30% of the passengers were dissatisfied with the air conditioning system. In order to improve the control of the indoor temperature as well as reduce the energy consumption of the air conditioning system, an improved zonal control strategy and AMPC control optimization algorithm based on real-time people are proposed, and different control strategies are modeled and simulated using MATLAB/Simulink. It is concluded that the improved zonal control method proposed in this paper can save 28.04% of the fan energy consumption compared with the traditional control strategy.

Cite

CITATION STYLE

APA

Zhou, P., Zhou, J., Tang, Y., Ma, Z., Yao, M., Zhu, J., & Si, H. (2024). An Improved Zonal Ventilation Control Method of Waiting Hall of High-Speed Railway Station Based on Real-Time Occupancy. Buildings, 14(6). https://doi.org/10.3390/buildings14061783