Disturbance detection in grid-connected distributed generation system using wavelet and S-transform

150Citations
Citations of this article
84Readers
Mendeley users who have this article in their library.
Get full text

Abstract

In this paper, wavelet transform and S-transform based approach is proposed for islanding detection and disturbance due to load rejection in distributed generation (DG) based hybrid system. The two types of distributed generation technology: inverter based and rotating machine based, that consists of photovoltaic, fuel cell and wind systems are considered in hybrid system configuration. The negative sequence voltage signal is analyzed through wavelet transform and S-transform for islanding detection of these resources from the grid. The above two approaches are also used in study of voltage profile at point of common coupling (PCC) with a non-linear load connected. The study for different scenarios in operation of DG system is presented in the form of time-frequency analysis. The energy content and standard deviation (STD) of S-transform contour and wavelet transform signal is also reported for both islanding detection and disturbance due to load rejection. © 2010 Elsevier B.V. All rights reserved.

Cite

CITATION STYLE

APA

Ray, P. K., Mohanty, S. R., & Kishor, N. (2011). Disturbance detection in grid-connected distributed generation system using wavelet and S-transform. Electric Power Systems Research, 81(3), 805–819. https://doi.org/10.1016/j.epsr.2010.11.011

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free