A qualitative investigation on double-skin façade fires

4Citations
Citations of this article
19Readers
Mendeley users who have this article in their library.

Abstract

Fire hazard of the green architectural feature double-skin façade is always a concern. A hazard scenario with a room fire adjacent to the façade was identified earlier after interviewing with fire professionals. Experimental studies on the consequence of the fire hazard due to trapping heat and mass in the façade cavity carried out before will be reported in this presentation. The rig was of height 15m with a fire chamber placed next to it. Flashover was induced to direct hot flame and smoke out. Only part of the building was studied instead of a full height façade due to resource limitations. Air temperature next to the upper interior glass pane was confirmed to be higher than the air temperature next to the exterior pane with normal air cavity depth in double-skin façades. Flame will then be diverted to the interior glass pane, giving possibility to spread fire to the upper rooms. © Owned by the authors, published by EDP Sciences, 2013.

Cite

CITATION STYLE

APA

Chow, C. L. (2013). A qualitative investigation on double-skin façade fires. In MATEC Web of Conferences (Vol. 9). EDP Sciences. https://doi.org/10.1051/matecconf/20130903007

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free