The Unified Power Quality Conditioner (UPQC) is one of the Custom Power devices (CP), and it mitigates both load current and supply voltage problems (voltage swells, sags, harmonics, etc.) simultaneously. By using CP, we are getting more familiar with renewable energy’s high penetration on the electrical grid because of its intermittent nature, which causes power flection. We are also using powered electronic devices, and non-linear loads produce harmonics that affect the voltage and current waveform. In this paper, a UPQC will be used with a sensitive load that is connected to a grid (grid–wind turbine) power system. The UPQC will operate under different disturbances such as phase-to-ground fault, non-linear load on the grid side, and non-linear load in parallel with the sensitive load, using pulse-width modulation and hysteresis as switching techniques. Simulation results using MATLAB/Simulink are used to compare the two pulsing-generating techniques and show that electrical power is continuously fed to the load in all disturbances with total harmonic distortion (THD) less than 5% for voltage and 4.5% for current.
CITATION STYLE
Mahdi, D. I., & Gorel, G. (2022). Design and Control of Three-Phase Power System with Wind Power Using Unified Power Quality Conditioner. Energies, 15(19). https://doi.org/10.3390/en15197074