Performance Assessment of R-454C, R-449A, and R-744 in Food Retail Refrigeration Systems †

6Citations
Citations of this article
8Readers
Mendeley users who have this article in their library.

Abstract

Reduced energy use and increased energy efficiency are essential for decarbonization and sustainable development. The food cold chain is a crucial infrastructure with high energy consumption and rising demand. A careful selection of technology used in food retail systems could result in long-term energy savings, functionality, ease of maintenance, and high energy efficiency. In this work, a comparison between the energy performance of three low-GWP refrigerants, namely, R-454C, R-449A, and R-744, is carried out with reference to an existing refrigerating system that serves a real supermarket. Energy usage and seasonal efficiency have been examined for three locations in Europe, representing mild and hot ambient temperatures. Results show that systems based on R-454C and R-449A perform significantly better than R-744 architectures, improving sCOP of up to +12% and +17%, respectively, with a simpler equipment design. This suggests that careful assessment is required to select the most appropriate refrigerant for each store size and climatic condition.

Cite

CITATION STYLE

APA

Ferretto, W., Molinaroli, L., & Codella, F. (2025). Performance Assessment of R-454C, R-449A, and R-744 in Food Retail Refrigeration Systems †. Energies, 18(3). https://doi.org/10.3390/en18030667