Enhanced optimal PMU placements with limited observability propagations

26Citations
Citations of this article
24Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

When the power grid encounters unexpected contingencies, conventional optimal phasor measurement units (PMUs) placement formulations with unlimited observability propagations may increase the risk of losing the observability. In order to tackle out this difficulty, an enhanced optimal PMU placement (OPP) formulation with considering bounded observability propagation constraints is proposed in this paper by introducing the concept of observability propagation depth (OPD). The OPD can characterize the depth of observability propagations applied to observe a bus from its nearest PMU measurements. To depict OPDs under a mathematical programming (MP) framework, new observability propagation rules, which are also valid for a power grid remaining incomplete observability with limited PMUs, are investigated. Extensive simulations are conducted on several IEEE test-bed systems as well as the Polish-2383 system to demonstrate the feasibility and the effectiveness of the proposed formulation.

Cite

CITATION STYLE

APA

Guo, X. C., Liao, C. S., & Chu, C. C. (2020). Enhanced optimal PMU placements with limited observability propagations. IEEE Access, 8, 22515–22524. https://doi.org/10.1109/ACCESS.2020.2967066

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free