Experimental study on HVAC sound parameters

7Citations
Citations of this article
26Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

HVAC system represent major source of buildings internal noise and therefore they are designed to provide a human acoustic comfort besides the thermal and air quality requirements. The paper experimentally investigates three types of commercial air handler units (AHU) with different ducts cross-section sizes and inlet-outlet configuration. The measurements are performed in an anechoic room. The measurements are carried out at different fan's speeds, ranging the power-charge from 30-100% while the duct air flow is slowly adjusted from full open to full closed, between 0-500 Pa. The sound pressure levels of the radiant units are rated using NR curves. Also, the supply and the outdoor ducts sound levels are compared in order to point the frequencies where the noise must be reduced. Third-octave band analysis of random noise of an air handling unit from a HVAC system is realized, using measurement procedures that agrees the requirements of the ISO 3744:2011 and ISO 5136:2010 standards. The comparatively results highlight the effects of the geometry, air flow pressure and power-charging dependencies upon the sound level. This is the start for a noise reduction strategy.

Cite

CITATION STYLE

APA

Bujoreanu, C., & Benchea, M. (2016). Experimental study on HVAC sound parameters. In IOP Conference Series: Materials Science and Engineering (Vol. 147). Institute of Physics Publishing. https://doi.org/10.1088/1757-899X/147/1/012051

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free