Abstract
This paper introduces a novel and improved double-resistor damped double-tuned passive power filter (DR-DDTF), designed using multi-objective optimization algorithms to mitigate harmonics and increase the hosting capacity of distribution systems with distributed energy resources. Although four different topologies of single-resistor damped double-tuned filters (DDTFs) have been studied before in the literature, the effectiveness of two different DR-DDTF configurations has not been examined. This work redresses this gap by demonstrating that via comprehensive simulations on two power systems, DR-DDTF provides better harmonic suppression and resonance mitigation than single-resistor alternatives. When it comes to optimizing the DR-DDTF for maximum hosting capacity and minimum system active power losses, the multi-objective artificial hummingbird outperformed six other algorithms in the benchmark. To allow for higher penetration of distributed generation without requiring grid upgrades, this newly developed harmonic mitigation filter provides a good alternative.
Cite
CITATION STYLE
Alhaider, M. M., Abdel Aleem, S. H. E., Ali, Z. M., & Zobaa, A. M. (2024). Harmonics management and hosting capacity enhancement: Optimal double-resistor damped double-tuned power filter with artificial hummingbird optimization. PLoS ONE, 19(5 May). https://doi.org/10.1371/journal.pone.0303207