Abstract
This article focuses on using machine learning to predict the distance at which a chemical storage tank fire reaches a specified thermal radiation intensity. DNV’s Process Hazard Analysis Software Tool (PHAST) is used to simulate different scenarios of tank leakage and to establish a database of tank accidents. Backpropagation (BP) neural networks, random forest models, and the optimized random forest model K-R are used for model training and consequence prediction. The regression performance of the models is evaluated using the mean squared error (MSE) and (Formula presented.). The results indicate that the K-R regression prediction model outperforms the other two machine learning algorithms, accurately predicting the distance at which the thermal radiation intensity is reached after a tank fire. Compared with the simulation results, the model demonstrates higher accuracy in predicting the distance of tank fire consequences, proving the effectiveness of machine learning algorithms in predicting the range of consequences of tank storage area fire events.
Author supplied keywords
Cite
CITATION STYLE
Zhong, W., Wang, S., Wu, T., Gao, X., & Liang, T. (2024). Optimized Machine Learning Model for Fire Consequence Prediction. Fire, 7(4). https://doi.org/10.3390/fire7040114