Abstract
Energy storage systems have been gaining attention as a means of load management in grid-interactive efficient buildings. This study investigated the physics of the ice storage tank (IST) and implemented an IST model in Modelica. The developed IST Modelica model was compared with a similar model in EnergyPlus and was validated against experimental data from a testbed at the National Institute of Standards and Technology. Three statistical performance metrics were used to quantify the accuracy of the IST model. Validation results (CV(RMSE) ≤ 10.20 %, NMBE ≤ 0.44 %) show that the proposed model has a good prediction accuracy according to ASHRAE Guideline 14.
Cite
CITATION STYLE
Li, G., Fu, Y., Pertzborn, A., Wen, J., & O’neill, Z. (2021). An Ice Storage Tank Modelica Model: Implementation and Validation. In Proceedings of 14th Modelica Conference 2021, Linköping, Sweden, September 20-24, 2021 (Vol. 181). Linköping University Electronic Press. https://doi.org/10.3384/ecp21181177