Abstract
Owing to use of mortar, which demonstrates low heat storage and discharge performance, conventional radiant floor-heating systems, based on the wet construction method and hot-water circulation, consume large amounts of energy. This study proposes a new type of radiant floor-heating system that is capable of reducing energy consumption via use of the latent heat of a phase change material (PCM), whereby the phase change, which occurs within, is induced by the thermal energy supplied by hot water. Simulation analyses revealed that hot-water supply temperatures, required to maintain the floor-surface and indoor-air temperatures at the set point using PCM latent heat, were in the range 40-41 °C. At supply water temperatures measuring less than 39 °C or exceeding 42 °C, the latent-heat effect of the phase change of the PCM tended to fail, and the corresponding floor-surface temperature assumed a value different from that corresponding to the set point. By contrast, supply temperatures in the range 40-41 °C resulted in return temperatures measuring approximately 27.4-27.5 °C, which in turn corresponded to an indoor air temperature of 21.6-22.6 °C that was stably maintained within ±0.6 °C of the 22 °C set-point temperature.
Author supplied keywords
Cite
CITATION STYLE
Baek, S., & Kim, S. (2018). Determination of optimum hot-water temperatures for PCM radiant floor-heating systems based on thewet construction method. Sustainability (Switzerland), 10(11). https://doi.org/10.3390/su10114004