Comparative testing of synchronized phasor measurement units

  • Depablos J
  • Centeno V
  • Phadke A
 et al. 
  • 4

    Readers

    Mendeley users who have this article in their library.
  • N/A

    Citations

    Citations of this article.

Abstract

This work reports the result of a comparative testing done on four phasor measurement units (PMU) from different manufacturers. Phase shift and attenuation at fundamental frequency, performance under system balanced and unbalanced conditions and performance under system variable frequency are the issues addressed for this comparative assessment. The results are presented in a comparative evaluation of features and performance of the PMU units. The results of this work reveal that data from the tested PMU units is of comparable accuracy only under nominal frequency operating conditions. At off-nominal frequency operation every tested PMU unit yielded a different phase and magnitude for the common measured voltage signal. The existing Synchrophasor standard does not specify phase or magnitude performance for off-nominal frequency operation. The standard is in the process of revision, and it is expected that the revised standard will specifically address performance requirements at off-nominal frequencies.

Author-supplied keywords

  • PMU units
  • Synchrophasor standard
  • comparative testing
  • off-nominal frequency operation
  • phase measurement
  • phasor measurement units
  • power system measurement
  • synchronized phasor measurement
  • system variable frequency

Get free article suggestions today

Mendeley saves you time finding and organizing research

Sign up here
Already have an account ?Sign in

Find this document

Authors

  • J. Depablos

  • V. Centeno

  • A.G. Phadke

  • M.R. Ingram

Cite this document

Choose a citation style from the tabs below

Save time finding and organizing research with Mendeley

Sign up for free