A study on effective length of long grounding conductor in windfarm

4Citations
Citations of this article
8Readers
Mendeley users who have this article in their library.

Abstract

This paper describes a study of grounding system of wind turbine generators in a windfarm. A horizontal grounding conductor is often used to obtain a low steady-state grounding resistance. The grounding resistance of the grounding conductor shows transient characteristics. Effective length of the grounding conductor is an important parameter to estimate peak value of lightning overvoltages on the grounding system. This paper proposes approximate formulas to investigate an influence of such parameters as soil resistivity and boundary condition of the grounding system on the effective length. © 2009 The Institute of Electrical Engineers of Japan.

Cite

CITATION STYLE

APA

Sekioka, S., & Funabashi, T. (2009). A study on effective length of long grounding conductor in windfarm. IEEJ Transactions on Power and Energy, 129(5). https://doi.org/10.1541/ieejpes.129.675