This work presents thermo-economic performance analyses of the absorption refrigeration system (ARS) having a capacity of 1 TR. The present ARS uses different types of biomass (wheat straw, rice straw, and soybean stalk) and produces a cooling effect at a temperature of 8 °C. The thermo-economic optimum generator temperature about 93.5 °C is obtained for the present ARS. In addition, the coefficient of performance (COP) is obtained about 0.678. The break-even point for the ARS is calculated about 10.8 years using wheat straw biomass. Further, the break-even point and biomass consumption are found the maximum for soybean stalk due to its higher cost and lower calorific value compared to wheat straw biomass.
CITATION STYLE
Modi, B., Patel, B., & Mudgal, A. (2020). Thermo-economic Analysis of Biomass-Powered Single Effect LiBr/H2O Absorption Refrigeration System. In Smart Innovation, Systems and Technologies (Vol. 161, pp. 87–97). Springer Science and Business Media Deutschland GmbH. https://doi.org/10.1007/978-981-32-9578-0_8