Investigation for a phase change immersion cooling system

1Citations
Citations of this article
4Readers
Mendeley users who have this article in their library.
Get full text

Abstract

In this paper, an immersion phase change cooling system is designed, in which an electronic fluoride solution is injected into the blade under the design background of the blade server. The system consists of four parallel blade servers with a maximum heating power of 1.2 kW per blade. When the submerged cooling system works normally, the liquid cooling medium is heated by the heating chip in the blade server and phase change occurs. The float continuous level gauge and the liquid cooling source control system make the heating resistance completely immersed in the electronic fluoride solution. The thermal resistance is used to simulate the heating of electronic devices, and a heat dissipation performance test system is established. The experimental results show that when the cooling system designed in this paper works normally, the surface temperature of the cooled heat source is below 70 C, and the temperature near the resistance on the outside of the blade fluctuates around 71.3 C. The system designed in this paper can run stably and effectively cool the heating parts in the blade.

Cite

CITATION STYLE

APA

Cai, Y., Xue, Y., Chen, X., Feng, Y., Wei, P., & Zheng, S. (2020). Investigation for a phase change immersion cooling system. In Lecture Notes in Electrical Engineering (Vol. 589, pp. 452–462). Springer Verlag. https://doi.org/10.1007/978-981-32-9441-7_46

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free