Current environmental diagnostics for the detection of Legionella fail to detect viable but non-culturable Legionella, have sensitivity limitations and are time-consuming (10–14 days to results). The objective of this study was to compare Legionella detection results between the standard ISO 11731 and an innovative Legionella detection method that utilizes a hybrid methodology of traditional microbiology and molecular detection. In this study, four hundred and seventy-six (476) potable building water samples were analyzed with ISO 11731 and the novel method in parallel. Of the 476 total samples that were tested, a discrepancy of 21% was observed when comparing the ISO 11731 method to the novel method. Separating the samples based on hazard control methods yielded a 15.4% discrepancy for chlorinated systems (n = 284) and a 29% discrepancy for monochloraminated systems (n = 192). The data presented here conclusively show inaccuracies in environmental validation for building water systems based on results returned by the standard ISO 11731 method. This is especially evident in systems primarily disinfected with monochloramines. Overall, these data highlight the need for new and innovative methods to overcome the inaccuracies of the traditional ISO 11731 spread plates to prevent disease and injury caused by Legionella.
CITATION STYLE
Wickenberg, L. P., Fisher, K. E., Cain, M. F., & McCoy, W. F. (2023). Inaccuracies of the ISO 11731 Method for Environmental Validation of Legionella in Building Water Systems: Opportunities to Improve Sensitivity and Detect Viable but Non-Culturable Legionella. Microorganisms, 11(1). https://doi.org/10.3390/microorganisms11010094
Mendeley helps you to discover research relevant for your work.