This study proposes an improved design for a typical sludge continuous feeding drying system connected with three air-source heat pumps. The system’s performance was further improved using air-deflectors on the drying chamber’s internal sidewalls, enhancing the heat and mass transfer between the conveyor sludge and circulating airflow. In this study, numerical analysis was performed to elucidate the deflector designs on the airflow field and thermal temperature field distributions in the drying chamber. The specific moisture extraction rate (SMER) value was quantified to evaluate the system’s overall improvement during experiments. With a suitable deflector design, the average percent water content in sludge could be further reduced to 22.2% with drying time of 18.3 h, and the SMER value could be enhanced from 1.38 kg/kWh to as high as 1.83 kg/kWh with an increment of 32.44%. Moreover, to prevent overloading and frequent shutdown of the compressors, an auxiliary cooling subsystem was designed to attain stable operational conditions. By the auxiliary cooling subsystem design, the compressors’ shutdown can be avoided, the temperature difference between airflow inlets and outlet of the drying chamber can be increased, and SMER value can be further increased to a value of 1.94 kg/kWh.
CITATION STYLE
Luo, W. J., Lin, C. Y., Wu, N. F., & Xu, Z. Q. (2020). Performance enhancement of a sludge continuous feed heat pump drying system by air deflectors and auxiliary cooling subsystems. Energies, 13(24). https://doi.org/10.3390/en13246651