Evaluation of ground-source variable refrigerant flow system for U.S. office buildings

1Citations
Citations of this article
9Readers
Mendeley users who have this article in their library.

Abstract

This paper evaluates the energy performance of ground-source variable refrigerant flow (VRF) systems to condition office buildings located in various U.S. climates. Specifically, the performance of the ground-source VRF systems was determined and evaluated against that achieved by conventional space heating and cooling systems, including packaged terminal air-conditioners (PTACs), water-source heat pumps (WSHPs), ground-source heat pumps (GSHPs), and water-source VRF systems. A comparative analysis shows that ground-source VRF systems require significantly lower source energy uses than other heating and cooling systems in all U.S. climates, ranging from 21% to 50% for PTACs, from 36% to 52% for WSHPs, from 22% to 49% for GSHPs, and from 4% to 19% for water-source VRFs. These results indicate that ground-source VRFs can be suitable heating and cooling systems for all U.S. climates when designing high-energy-performance commercial buildings.

Cite

CITATION STYLE

APA

Kwag, B. C., & Krarti, M. (2018). Evaluation of ground-source variable refrigerant flow system for U.S. office buildings. Sustainability (Switzerland), 10(5). https://doi.org/10.3390/su10051621