The article deals with the development of CFD model of natural draft wet-cooling tower flow. The physical phenomena taking place within a natural draft wet cooling tower are described by the system of conservation law equations along with additional equations. The heat and mass transfer in the counterflow wet-cooling tower fill are described by model [1] which is based on the system of ordinary differential equations. Utilization of model [1] of the fill allows us to apply commonly measured fill characteristics as shown by [2].The boundary value problem resulting from the fill model is solved separately. The system of conservation law equations is interlinked with the system of ordinary differential equations describing the phenomena occurring in the counterflow wet-cooling tower fill via heat and mass sources and via boundary conditions. The concept of numerical solution is presented for the quasi one dimensional model of natural draft wet-cooling tower flow. The simulation results are shown. © 2014 EDP Sciences.
Mendeley helps you to discover research relevant for your work.
CITATION STYLE
Hyhlík, T. (2014). Concept of CFD model of natural draft wet-cooling tower flow. In EPJ Web of Conferences (Vol. 67). EDP Sciences. https://doi.org/10.1051/epjconf/20146702044