Improved three-phase AFD islanding detection based on digital control and non-detection zone elimination

6Citations
Citations of this article
7Readers
Mendeley users who have this article in their library.

Abstract

This paper proposes an improved active frequency drift (AFD) islanding detection method of a three-phase inverter. Different than the existing single-phase AFD method, in the three-phase system, the disturbance is added to the phase angle, which takes part in coordinate transformation calculations. Thus, the frequency drift of the three-phase reference current can be realized by the disturbance of the phase angle. It is unnecessary to add frequency drift to each phase respectively with the proposed method, which can simplify the control system. Furthermore, the non-detection zone can be eliminated by updating certain parameters; therefore, the detection method is sensitive. In this paper, the application of the proposed method in a digital control system is discussed in detail. The non-detection zone is analyzed, and an elimination method is proposed. Finally, the simulation and experimental results are given to verify the theoretical analysis.

Cite

CITATION STYLE

APA

Zheng, X., Zhang, R., Chen, X., & Sun, N. (2018). Improved three-phase AFD islanding detection based on digital control and non-detection zone elimination. Energies, 11(9). https://doi.org/10.3390/en11092421