Oil field retrofit of ESPs to meet harmonic compliance

15Citations
Citations of this article
29Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

A large petrochemical company installed nearly 50 000 hp of electrical submersible pumps (ESPs) at an existing midwest U.S. oil field. Being equipped with adjustable-speed drives (ASDs), these ESPs introduced high levels of current harmonic distortion, which resulted in 14%-19% voltage harmonic distortion at the electrical utility supply. Initially, the utility noticed the low power factor (PF) and had the oil company pay for the installation of power factor correction (PFC) capacitors on their medium-voltage supply. Once installed, the utility began to have problems with these capacitors and continued to receive complaints from other customers adjacent to the oil field; thus, they enforced harmonic limits, as defined by IEEE Std 519, at all points of common coupling. Measurements were made with a harmonic analyzer at several locations throughout the electrical system to quantify harmonics and determine the effect the ESPs were having on the utility distribution system. Computer simulations were performed to analyze different methods of harmonic mitigation. Ultimately, passive harmonic filters were installed on all ESPs in phases. In addition, the PFC capacitors were permanently disconnected after determining that a power system resonance condition existed. Once all phases of the project were complete, the voltage distortion level decreased to below 5%, and PF improved to near unity without the PFC capacitors. This paper will describe the effect of harmonics on the electrical distribution system caused by ASDs, practical solutions to excessive voltage harmonic distortion, resonance issues with PFC capacitors, and the challenges associated with different methods of harmonic mitigation.

Cite

CITATION STYLE

APA

Farbis, M., Hoevenaars, A. H., & Greenwald, J. L. (2016). Oil field retrofit of ESPs to meet harmonic compliance. IEEE Transactions on Industry Applications, 52(1), 718–728. https://doi.org/10.1109/TIA.2015.2481358

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free