With the intention of keep the customer voltage within a nominal voltage boundary (the South Korea voltage regulation in range of 220 V ± 6% for a single phase), the SVR (step voltage regulator) method in the primary feeder has been seriously systematized for the scheduled tap time delay (from a minimum of 120 s to a maximum of 900 s). The voltage must be compensated for the primary feeder during the tap delay time of SVR. However, when RES (renewable energy resource) is connected with the primary feeder, the customer voltage could exceed the nominal voltage boundary. Therefore, in order to keep the secondary feeder voltage within the nominal voltage boundary at all the time, this paper proposed a novel voltage control method in the primary feeder using coordinated controls between ESS (energy storage system) and SVR. Through the simulations based on PSCAD/EMTDC which is analysis tool of power system, it is confirmed that the proposed algorithm can effectively control the customer voltage within allowable limitation.

Cite

CITATION STYLE

APA

Kim, B., Nam, Y. H., Ko, H., Park, C. H., Kim, H. C., Ryu, K. S., & Kim, D. J. (2019). Novel voltage control method of the primary feeder by the energy storage system and step voltage regulator. Energies, 12(17). https://doi.org/10.3390/en12173357