Horizontal ground heat exchangers (HGHEs) have advantages such as convenient construction and low cost; however, their application and popularization are restricted owing to traditional linear HGHEs occupying large space and presenting low total heat transfer capacity. Spiral-coil and slinky-coil HGHEs have been proposed, but currently a comprehensive comparison and evaluation for these types of HGHEs are still needed. In this study, a three-dimensional heat transfer model of the three types of HGHEs for ground source heat pumps (GSHPs) was established. Based on the simulation results, the long-term heat transfer performances were investigated, including the temperature field of surrounding energystorage soils, outlet working fluid temperature, coefficient of performance (COP) of units, and surplus temperature of the energy-storage soils. A new concept named heat transfer capacity per heat-affected area was proposed in this paper. It is found that the spiral-coil HGHEs have the best performances in terms of working-fluid outlet temperature, unit COP, total heat transfer capacity, heat transfer rate heat-affected area. The linear HGHEs shows the best performances in terms of mitigating heat imbalance risk and heat transfer rate per length. The results provide a reliable basis for selection of HGHE types in engineering practice and improvement guide in the future.
CITATION STYLE
Zou, H., Pei, P., Wang, C., & Hao, D. (2021). A numerical study on heat transfer performances of horizontal ground heat exchangers in ground-source heat pumps. PLoS ONE, 16(5 May). https://doi.org/10.1371/journal.pone.0250583