The Effect of Refrigerant Charge on the Performance of a Split-Unit Type Air Conditioner Using R22 Refrigerant

4Citations
Citations of this article
12Readers
Mendeley users who have this article in their library.

Abstract

Numerous air conditioners are running without a proper refrigerant charge due to leakage and improper charging during installation. Therefore, there is a need to understand the performance of the air conditioner if it is not properly charged for the means of optimal operation and cost saving. This study is focusing on the usage of a used small capacity split-unit type air conditioner using R-22 refrigerant. The objective is to study the condenser performance over a variation of refrigerant charges. From the results, it is clear that the optimum refrigerant charge is 100%. The highest cooling capacity and COP were 3,330 J/s and 3.05 respectively.

Cite

CITATION STYLE

APA

Yusof, M. H., Muslim, S. M., Suhaimi, M. F., Ibrahim, H., Aziz, A. A., & Basrawi, M. F. (2018). The Effect of Refrigerant Charge on the Performance of a Split-Unit Type Air Conditioner Using R22 Refrigerant. In MATEC Web of Conferences (Vol. 225). EDP Sciences. https://doi.org/10.1051/matecconf/201822502011