Identification of Lightning Stroke and Fault in the Travelling Wave Protection

  • Zou G
  • Gao H
  • Su W
  • et al.
N/ACitations
Citations of this article
8Readers
Mendeley users who have this article in their library.

Abstract

To resolve the impact of transient high frequency signals induced by lightning stroke on the travelling wave protection of transmission line, a novel identification algorithm is proposed. Using the characteristics of symmetric current wave-form induced by lightning stroke without causing fault and that of asymmetric current waveform generated by fault within a very short time interval, the waveform of transient current above and below time-axes are integrated respec-tively. First, through comparing the relative ratio of them with threshold value, the primary criterion identifying fault and lightning stroke is constructed; Secondly, to improve the reliability of discrimination between lightning stroke with and without causing fault, according to the difference of them, the secondary criterion is also defined. The simulation results and analysis demonstrate that the proposed integral criterions are valid and correct.

Cite

CITATION STYLE

APA

Zou, G., Gao, H., Su, W., & Wang, D. (2009). Identification of Lightning Stroke and Fault in the Travelling Wave Protection. Journal of Electromagnetic Analysis and Applications, 01(01), 31–35. https://doi.org/10.4236/jemaa.2009.11006

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free