Performance analysis of an integrated heat pump with air-conditioning system for the existing hospital building application

11Citations
Citations of this article
42Readers
Mendeley users who have this article in their library.

Abstract

In this study, a complete evaluation procedure of energy-saving and efficiency improvement for a large-scale hospital retrofit project has been established and successfully validated in Taiwan. The retrofit scheme, in integrating the alternative hot water system, namely, a water source heat pump (WSHP), with the existing HVAC (Heating, Ventilating, and Air-Conditioning) system, enables the capability to meet the cooling and hot water demand simultaneously with a larger safety margin as well as saving energy. In addition, it has been found that the integrated system provides a new source for cooling which can be utilized as a system redundancy in avoiding system shutdown. This is very useful when considering in specific areas in the hospital, such as intensive care unit, or operation rooms, where cooling should not be interrupted on any occasion. In this study, it is validated that the coefficient of performance (COP) of the newly added WSHP system, under heating and cooling mode, is 3.62 and 2.62, respectively. The recorded annual cost reduction by this integrated system is $102,564, with a payback of 1.2 years. The hospital after retrofit has been operating safer, with more redundancy, and more energy-efficient which warrants tremendous potential for implementation in the industry.

Cite

CITATION STYLE

APA

Chiang, C. Y., Yang, R., Yang, K. H., & Lee, S. K. (2017). Performance analysis of an integrated heat pump with air-conditioning system for the existing hospital building application. Sustainability (Switzerland), 9(4). https://doi.org/10.3390/su9040530

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free