The presence of a low DC voltage in a power grid produces an excitation asymmetry for the distribution transformers, resulting in unwanted half-cycle saturation that may impair transformer safety, reliability and efficiency, especially in increasing the reactive power, stray losses and iron losses. This paper highlights a diagnostic method based on the phase value of the particular even harmonics of a transformer excitation current as the basic marker of an excitation asymmetry. In order to achieve a straightforward insight into the nature of even harmonics behaviour, a novel method of decomposition an excitation current waveform into its unhysteretic (pure magnetization) and hysteretic components has been included in the harmonic analysis.
CITATION STYLE
Pjevalica, N., Petrovic, N., Pjevalica, V., & Teslic, N. (2016). Experimental detection of transformer excitation asymmetry through the analysis of the magnetizing current harmonic content. Elektronika Ir Elektrotechnika, 22(2), 43–48. https://doi.org/10.5755/j01.eie.22.2.14590