In this investigation, the measurement thermal parameters and thermal comfort field survey were carried in six air-conditioned hospitals in Guangzhou. A total of 114 valid questionnaires were collected. Based on the data, there were strong linear regression relationships between PMV and MTSV and operative temperature. The neutral temperature was 24.39 °C from the linear regression of MTSV. The thermal comfort temperature which meets a satisfaction degree of 90% or 80% ranges from 22.83 to 25.94 °C, 21.74 to 27.03. In addition, the neutral operation temperature was 23.75 °C from the PMV model. The thermal comfort temperature which meets a satisfaction degree of 90% or 80% ranges from 22.00 to 25.50 °C, 20.77 to 26.73. Comparing the MTSV and PMV, the MTSV was lower than that of PMV. The preference Top was obtained by Probit regression analysis curve intersection point was 24.43 °C. By Actual Percentage Dissatisfaction obtains 90% or 80% of the medical staff acceptable comfort temperature upper limit of 24.71 °C, 25.53 °C.
CITATION STYLE
Ji, X., Fang, Z., Zheng, Z., & Ji, Z. (2020). Investigation into the Adaption of PMV to Evaluation of the Medical Staff in Hospitals in Guangzhou. In Environmental Science and Engineering (pp. 755–764). Springer. https://doi.org/10.1007/978-981-13-9520-8_78