Thermodynamic and Economic Performance Assessment of Double-Effect Absorption Chiller Systems with Series and Parallel Connections

3Citations
Citations of this article
18Readers
Mendeley users who have this article in their library.

Abstract

Absorption cooling technologies converting excess heat and renewable heat resources to cooling energy have shown progress in recent years. In this study, two 400 kW LiBr solution absorption chiller types with series and parallel connected are analyzed over a range of parameter values to better understand their applicability for different uses. Thermodynamic models for the components were constructed and validated. The performance of the chillers related to heat transfer, energy, exergy, and economy performance was comprehensively analyzed. The operating performance was investigated by considering the external variables, including inlet cooling water, chilled water, and inlet steam temperatures and the solution allocation ratio. The results indicate that the parallel connected chiller reaches higher energy and exergy performance than the series-connected chiller, but the heat transfer and economic performance was lower. The coefficient of performance and the exergy efficiency of the parallel chiller were for the reference system 1.30 and 24.42%, respectively. Except for the exergy efficiency, the inlet steam and inlet chilled water temperature had positive impact on the heat transfer, energy, and economic performance, while the inlet cooling water temperature trends the opposite. The sensitivity analysis on solution allocation ratio showed that a higher ratio decreases the heat transfer and economic performance, but considering the energy and exergy performance, a suitable allocation ratio would be 0.54.

References Powered by Scopus

Review of solar sorption refrigeration technologies: Development and applications

230Citations
N/AReaders
Get full text

Energetic and financial investigation of a stand-alone solar-thermal Organic Rankine Cycle power plant

218Citations
N/AReaders
Get full text

Solar-powered absorption chillers: A comprehensive and critical review

201Citations
N/AReaders
Get full text

Cited by Powered by Scopus

Applications of geothermal sources for absorption chillers as efficient and clean cooling technologies for buildings: A comprehensive review

12Citations
N/AReaders
Get full text

Comparisons and optimization of two absorption chiller types by considering heat transfer area, exergy and economy as single-objective functions

1Citations
N/AReaders
Get full text

Energy-saving and carbon reduction analysis of series/parallel combination for heat pump and chiller in a hotel building

0Citations
N/AReaders
Get full text

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Cite

CITATION STYLE

APA

Hu, J., Teng, K., Qiu, Y., Chen, Y., Wang, J., & Lund, P. (2022). Thermodynamic and Economic Performance Assessment of Double-Effect Absorption Chiller Systems with Series and Parallel Connections. Energies, 15(23). https://doi.org/10.3390/en15239105