20 kv Pajajaran feeder as one of the suppliers that resembles electrical energy to Jakabaring Sport City (JSC). The reliability of the 20 kV voltage distribution affects the XVIII ASEAN GAMES event at Jakabaring Sport City (JSC). The fundamental problems in the distribution of electric power are the quality, continuity and availability of electrical power services to customers. Reliability illustrates a measure of the level of service of electricity supply from a system greatly influenced by system configuration, safety devices installed and protection systems. To determine the reliability of Pajajaran 20 kV, a reliability index is determined, namely the magnitude to compare the appearance of a distribution system. Reliability index with Section Technique Method to find out indicators that are expressed in probability quantities. Reliability index load points that are usually used include the average load termination rate, average time out and load termination average system reliability index that is widely used, among others, Section Technique Method on the Average Interruption duration Index (SAIDI) system obtained value 2 , 5707 hours / mop and the Average Interruption Frequency Index (SAIFI) Section Technique Method obtained a value of 2.6933 times / mop
CITATION STYLE
Putra, D. E., & Nurhadiyanto, M. (2019). ANALISIS KEANDALAN PENYULANG PAJAJARAN 20KV MENGGUNAKAN METODE SECTION TECHNIQUE UNTUK ASIAN GAMES XVIII DI PALEMBANG. Jurnal Ampere, 4(1), 222. https://doi.org/10.31851/ampere.v4i1.3469