Generally two-level voltages are adopted for DC building power supply system. From the point of view of human beings safety, only the lower level voltage which may be contacted barehanded is discussed in this paper based on the related safety thresholds of human beings current effect. For several voltage levels below 100V recommended by IEC, the body current and current density of human electric shock under device normal work condition, as well as effect of unidirectional single impulse currents of short durations are calculated and analyzed respectively. Finally, DC 60V is recommended as the lower level rating voltage through the comprehensive consideration of technical condition and cost of safety criteria.
CITATION STYLE
Wang, Z., Yu, K., Xie, G., & Zou, J. (2018). The Rated Voltage Determination of DC Building Power Supply System Considering Human Beings Safety. In IOP Conference Series: Earth and Environmental Science (Vol. 108). Institute of Physics Publishing. https://doi.org/10.1088/1755-1315/108/5/052094