Safety issues referred to induced sheath voltages in high-voltage power cables-case study

8Citations
Citations of this article
19Readers
Mendeley users who have this article in their library.

Abstract

Load currents and short-circuit currents in high-voltage power cable lines are sources of the induced voltages in the power cables' concentric metallic sheaths. When power cables operate with single-point bonding, which is the simplest bonding arrangement, these induced voltages may introduce an electric shock hazard or may lead to damage of the cables' outer non-metallic sheaths at the unearthed end of the power cable line. To avoid these aforementioned hazards, both-ends bonding of metallic sheaths is implemented but, unfortunately, it leads to increased power losses in the power cable line, due to the currents circulating through the sheaths. A remedy for the circulating currents is cross bonding-the most advanced bonding solution. Each solution has advantages and disadvantages. In practice, the decision referred to its selection should be preceded by a wide analysis. This paper presents a case study of the induced sheath voltages in a specific 110 kV power cable line. This power cable line is a specific one, due to the relatively low level of transferred power, much lower than the one resulting from the current-carrying capacity of the cables. In such a line, the induced voltages in normal operating conditions are on a very low level. Thus, no electric shock hazard exists and for this reason, the simplest arrangement-single-point bonding-was initially recommended at the project stage. However, a more advanced computer-based investigation has shown that in the case of the short-circuit conditions, induced voltages for this arrangement are at an unacceptably high level and risk of the outer non-metallic sheaths damage occurs. Moreover, the induced voltages during short circuits are unacceptable in some sections of the cable line even for both-ends bonding and cross bonding. The computer simulations enable to propose a simple practical solution for limiting these voltages. Recommended configurations of this power cable line-from the point of view of the induced sheath voltages and power losses-are indicated.

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Cite

CITATION STYLE

APA

Czapp, S., & Dobrzynski, K. (2020). Safety issues referred to induced sheath voltages in high-voltage power cables-case study. Applied Sciences (Switzerland), 10(19). https://doi.org/10.3390/APP10196706

Readers over time

‘20‘21‘22‘23‘24036912

Readers' Seniority

Tooltip

PhD / Post grad / Masters / Doc 4

57%

Researcher 2

29%

Professor / Associate Prof. 1

14%

Readers' Discipline

Tooltip

Engineering 6

86%

Pharmacology, Toxicology and Pharmaceut... 1

14%

Save time finding and organizing research with Mendeley

Sign up for free
0