Design and Test of an Air Coil Superconducting Fault Current Limiter Demonstrator

41Citations
Citations of this article
24Readers
Mendeley users who have this article in their library.
Get full text

Abstract

This paper discusses the design, set-up and short-circuit testing of an air coil superconducting fault current limiter demonstrator. The demonstrator was specified for 60 kVA, 400 V, z = 6%. It consists of a primary winding made of copper, which is basically the equivalent of an air core reactor and a secondary superconducting winding made of commercially available (RE)BCO tapes, which are individually short-circuited. Both windings are inductively coupled and intended to work in liquid nitrogen. The measurements results show significantly lower impedance during normal operation compared to the air core reactor. If a fault current occurs the induced current in the secondary winding quenches the superconducting tapes, which generates a resistance and significantly increasing the impedance of the limiter. The built demonstrator achieves a current limiting capability of up to 40% for fault currents 17 times higher than the nominal current. The demonstrator proves the concept of the air coil superconducting fault current limiter and verifies the underlying design method.

Cite

CITATION STYLE

APA

Naeckel, O., & Noe, M. (2014). Design and Test of an Air Coil Superconducting Fault Current Limiter Demonstrator. IEEE Transactions on Applied Superconductivity, 24(3). https://doi.org/10.1109/TASC.2013.2286294