Abstract
This paper performs an investigation on electromagnetic transients for a practical 500 kV cable system. The system consists of 500 kV overhead lines, submarine and underground cables. In order to study the insulation coordination of the cable system, the transient simulations are performed using EMTP. The modal propagation constants of submarine cable are also investigated. Moreover, the cable series and shunt parameters are calculated using the newly developed Line/Cable Data Module in EMTP. The voltage and current characteristics of the cable system in steady-state, and for switching, fault and lightning transients, are studied. The transient overvoltage levels are also compared with requirements of insulation coordination in local standards. The work shown in this paper could provide a reference for the insulation design of 500 kV cable system.
Author supplied keywords
Cite
CITATION STYLE
Jiang, N., Yang, C., Xue, H., & Mahseredjian, J. (2023). An investigation of electromagnetic transient characteristics on a practical 500 kV submarine cable system. Electric Power Systems Research, 223. https://doi.org/10.1016/j.epsr.2023.109615