Fire source localization based on distributed temperature sensing by a dual-line optical fiber system

47Citations
Citations of this article
16Readers
Mendeley users who have this article in their library.

Abstract

We propose a method for localizing a fire source using an optical fiber distributed temperature sensor system. A section of two parallel optical fibers employed as the sensing element is installed near the ceiling of a closed room in which the fire source is located. By measuring the temperature of hot air flows, the problem of three-dimensional fire source localization is transformed to two dimensions. The method of the source location is verified with experiments using burning alcohol as fire source, and it is demonstrated that the method represents a robust and reliable technique for localizing a fire source also for long sensing ranges.

Cite

CITATION STYLE

APA

Sun, M., Tang, Y., Yang, S., Li, J., Sigrist, M. W., & Dong, F. (2016). Fire source localization based on distributed temperature sensing by a dual-line optical fiber system. Sensors (Switzerland), 16(6). https://doi.org/10.3390/s16060829