Dynamic thermal modelling of horizontal ground-source heat pumps

37Citations
Citations of this article
37Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

A computer program has been developed for numerical simulation of the dynamic thermal performance of horizontally coupled heat exchangers for ground-source heat pumps, taking account of dynamic variations of climatic, load and soil conditions. The program was used to investigate the effects of operating and start times, installation depth and soil freezing on the heat exchanger performance. It is shown that the rate of heat extraction decreases with increasing operating time. Operating a heat pump with an earlier start date in autumn would give rise to a higher amount of cumulative heat extraction. Also, a heat exchanger installed at a shallower depth can provide a larger heat extraction rate at the early stage of heating operation. In addition, soil freezing enhances heat extraction. © The Author 2013. Published by Oxford University Press.

Cite

CITATION STYLE

APA

Gan, G. (2013). Dynamic thermal modelling of horizontal ground-source heat pumps. International Journal of Low-Carbon Technologies, 8(2), 95–105. https://doi.org/10.1093/ijlct/ctt012

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free