Abstract
SNCR (Selective non-catalytic reduction) Technology is currently being used to reach the emission limit for nitrogen oxides at fossil fuel fired power plant and/or heating plant and optimum temperature for SNCR process is in range 850 - 1050°C. Modified SNCR technology is able to reach reduction 60% of nitrogen oxides at temperature up to 1250°C. So the technology can also be installed where the flue gas temperature is too high in combustion chamber. Modified SNCR was tested using generally known SNCR chemistry implemented in CFD (Computation fluid dynamics) code. CFD model was focused on detail simulation of reagent injection and influence of flue gas temperature. Than CFD simulation was compared with operating data of boiler where the modified SNCR technology is installed. By comparing the experiment results with the model, the effect on nitrous oxides removal process and temperature of flue gas at the injection region.
Cite
CITATION STYLE
Blejchař, T., Konvička, J., Von Der Heide, B., Malý, R., & Maier, M. (2018). High Temperature Modification of SNCR Technology and its Impact on NOx Removal Process. In EPJ Web of Conferences (Vol. 180). EDP Sciences. https://doi.org/10.1051/epjconf/201818002009