Abstract
A two-dimensional steady-state numerical model is developed to study the heat transfer in a run-around heat recovery system with two exchangers each with a combination of counter and cross (counter/cross) flow between parallel plates or membranes. A finite difference method is used to solve the steady-state equations of continuity, momentum and heat transfer. The simulated values for the effectiveness of each counter/cross flow heat exchanger and the overall run-around system are used to develop effectiveness correlations which agree within ±2% of the simulated effectiveness of individual heat exchangers and overall system. It is shown that the effectiveness of this new run-around heat exchanger (RAHE) falls between the effectiveness of similar run-around systems with either two cross-flow exchangers or two counter-flow exchangers. For a given total surface area of the exchangers, the highest overall sensible effectiveness is achieved with exchangers which have a small exchanger aspect ratio and relatively small solution flow inlet and outlet lengths. © 2009 Elsevier Ltd. All rights reserved.
Author supplied keywords
Cite
CITATION STYLE
Vali, A., Simonson, C. J., Besant, R. W., & Mahmood, G. (2009). Numerical model and effectiveness correlations for a run-around heat recovery system with combined counter and cross flow exchangers. International Journal of Heat and Mass Transfer, 52(25–26), 5827–5840. https://doi.org/10.1016/j.ijheatmasstransfer.2009.07.020
Register to see more suggestions
Mendeley helps you to discover research relevant for your work.