A community-wide outbreak of legionnaires disease linked to industrial cooling towers - How far can contaminated aerosols spread?

260Citations
Citations of this article
189Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

A community-wide outbreak of legionnaires disease occurred in Pas-de-Calais, France, in November 2003-January 2004. Eighteen (21%) of 86 laboratory-confirmed cases were fatal. A case-control study identified smoking, silicosis, and spending >100 min outdoors daily as risk factors for acquiring the disease. Legionella pneumophila strain Lens was isolated from cooling towers, wastewater, and air samples from plant A. This unique strain matched all 23 clinical isolates, as assessed by pulsed-field gel electrophoresis subtyping. Modeling of atmospheric dispersion of aerosols emitted from plant A cooling towers showed good coverage of the communes where patients lived and showed that the dispersion extended over a distance of at least 6 km from plant A. No other aerosol-producing installation was identified as a plausible source, and no common source of indoor exposure was found. These findings implicate plant A as the most likely outbreak source and suggest that the distance of airborne transmission of L. pneumophila may be greater than previously reported. © 2005 by the Infectious Diseases Society of America. All rights reserved.

Cite

CITATION STYLE

APA

Nguyen, T. M. N., Ilef, D., Jarraud, S., Rouil, L., Campese, C., Che, D., … Desenclos, J. C. (2006). A community-wide outbreak of legionnaires disease linked to industrial cooling towers - How far can contaminated aerosols spread? Journal of Infectious Diseases, 193(1), 102–111. https://doi.org/10.1086/498575

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free