Export transformer switching transient mitigation in hvdc connected offshore wind farms

9Citations
Citations of this article
17Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

An increasing number of offshore wind farms are connected to the public grid with large-scale HVDC links. The electrical transients caused by the energization of the export transformers appear more significant in the converter-driven offshore AC grid with low short-circuit power, than in direct AC grid connections. This may lead to a violation of the 2% voltage dip criterion, thus seriously affecting the production of neighboring wind farms. Additionally, the transformer and the entire insulation system are exposed to mechanical and dielectric stress. This paper investigates the influence of three factors, namely excitation, switching angle, and remnant core magnetization, onto the inrush current. Electromagnetic transient simulations and field measurements show that with a smart use of the on load tap changer, point on wave switching, and a demagnetization of the core by a cable-shunt swing circuit, the three factors above can be used as degrees-of-freedom to effectively mitigate the inrush current phenomenon.