Principle of Flexible Ground-Fault Arc Suppression Device Based on Zero-Sequence Voltage Regulation

36Citations
Citations of this article
9Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

Single-line-to-ground (SLG) fault arcs cause the intermittent over-voltages, leading to short circuits within large-scale area. In this paper, a flexible arc suppression device is proposed, which adopts a zigzag grounding transformer, multi-terminal breakers and an isolation transformer to regulate zero-sequence voltage. Principle of zero-sequence voltage regulation (ZVR) and arc suppression method is presented. By carefully choosing the secondary side voltages of grounding transformer as the input of isolation transformer, the zero-sequence voltage is nearly constrained to the opposite of faulty phase supply voltage, and the ground-fault current is limited to a very small value. This device has high adaptability for low-resistance ground fault as it doesn't adopt any electronic apparatus. A 10kV prototype was established and multiple fault conditions were experimented to verify the effectiveness of the proposed ZVR device and its arc suppression principle.

Cite

CITATION STYLE

APA

Fan, B., Yao, G., Yu, K., Zeng, X., Wang, W., Zhuo, C., & Guerrero, J. M. (2021). Principle of Flexible Ground-Fault Arc Suppression Device Based on Zero-Sequence Voltage Regulation. IEEE Access, 9, 2382–2389. https://doi.org/10.1109/ACCESS.2020.3047188