Abstract
The stationary power market, particularly telecommunications back-up (telecom) applications, is dominated by lead-acid batteries. A large percentage of telecom powerplants are housed in outdoor enclosures where valve-regulated lead-acid (VRLA) batteries are commonly used because of their low-maintenance design. Batteries in these enclosures can be exposed to temperatures which can exceed 70◦C, significantly reducing battery life. Nickel–cadmium (Ni–Cd) batteries have traditionally been deployed in hotter locations as a high-temperature alternative to VRLA. This paper compares the performances of nickel/metal hydride (Ni/MH), Ni–Cd, and VRLA batteries in a simulated telecom environment according to published testing standards. Among these three choices, Ni/MH batteries showed the best overall performance, suggesting substantially longer operating life in high temperature stationary use.
Author supplied keywords
Cite
CITATION STYLE
Zelinsky, M. A., Koch, J. M., & Young, K. H. (2018). Performance comparison of rechargeable batteries for stationary applications (Ni/MH vs. Ni–Cd and VRLA). Batteries, 4(1). https://doi.org/10.3390/batteries4010001