Overvoltages due to synchronous tripping of plug-in electric-vehicle chargers following voltage dips

26Citations
Citations of this article
52Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

Plug-in electric vehicle (PEV) charging equipment incorporates protection that ensures that grid disturbances do not damage the charger or vehicle. When the grid voltage sags below 80% of nominal, undervoltage protection is likely to disconnect the charging load from the grid. Most PEV charging will occur overnight, when non-PEV load is at a minimum. This paper argues that PEV voltage-sag response, when synchronized across large numbers of PEVs, could result in the loss of a significant proportion of the total load. It is shown that this load loss can lead to unacceptably high voltages once the initiating event has been cleared. This paper explores the nature of this voltage-rise phenomenon. Analysis tools are developed to assist in determining PEV loading conditions that demarcate acceptable postdisturbance voltage response from unacceptable outcomes. Two examples, based on standard distribution test systems, are used to illustrate PEV-induced overvoltage behavior, and demonstrate applications of the analysis tools. © 1986-2012 IEEE.

Cite

CITATION STYLE

APA

Kundu, S., & Hiskens, I. A. (2014). Overvoltages due to synchronous tripping of plug-in electric-vehicle chargers following voltage dips. IEEE Transactions on Power Delivery, 29(3), 1147–1156. https://doi.org/10.1109/TPWRD.2014.2311112

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free