Abstract
It is pointed out that safe loading of transformers by temperature requires not only an accurate knowledge of the thermal laws but also a knowledge of what is a safe temperature limit to be maintained continuously which condition seldom, if ever, happens with the present method of limiting the load to nameplate rating. In view of our present knowledge and experience the author questions the advisability of loading transformers continuously up to the present A. I. E. E. limit of 105 deg. cent. hot spot and argues for the establishment of a differential of 10 deg. cent. between the limit to be maintained continuously by means of overloads and the limit to be reached occasionally with rated load. In other words, for continuously maintained maximum temperatures the hot spot should not exceed 95 deg. cent. It is shown by the use of the thermal laws that without increasing the maximum or hot spot temperature, transformers can be overloaded 1 per cent for each degree centigrade by which the ambient is below 30 deg. cent. (air) for self-cooled transformers, 25 deg. (water) for water-cooled transformers. The results of laboratory aging tests conducted on class A insulations in air and in oil are given. These tests show that the rate of aging is roughly double for each 8 deg. cent. increase in temperature. By the use of these data and by integrating the hot spot temperature rise curve resulting from different load factors the permissible peak load which causes the same deterioration in the insulation as a steady load is obtained. By combining the two rules, increased kv-a. with lower ambients and increased kv-a. with lower load factors, there is obtained a series of loading curves giving the permissible kv-a. capacities for different cooling mediums and load factors. On the average, these curves are conservative because they apply to transformers having quite a wide range of characteristics which affect the temperature rise. Maximum and minimum bi-monthly and average annual outdoor temperatures as furnished by the Bureau of Standards are given for various localities throughout the United States. Copyright 1930. By A. I. E. E.
Cite
CITATION STYLE
Montsinger, V. M. (1930). Loading Transformers By Temperature. Transactions of the American Institute of Electrical Engineers, 49(2), 776–790. https://doi.org/10.1109/T-AIEE.1930.5055572
Register to see more suggestions
Mendeley helps you to discover research relevant for your work.