Abstract
This paper describes a current differential relay for transformer protection that operates in conjunction with a core saturation detection-based blocking algorithm. The differential current for the magnetic inrush or over-excitation has a point of inflection at the start and end of each saturation period of the transformer core. At these instants, discontinuities arise in the first-difference function of the differential current. The second- and third-difference functions convert the points of inflection into pulses, the magnitudes of which are large enough to detect core saturation. The blocking signal is activated if the third-difference of the differential current is larger than the threshold and is maintained for one cycle. In addition, a method to discriminate between transformer saturation and current transformer (CT) saturation is included. The performance of the proposed blocking scheme was compared with that of a conventional harmonic blocking method. The test results indicate that the proposed scheme successfully discriminates internal faults even with CT saturation from the magnetic inrush, over-excitation, and external faults with CT saturation, and can significantly reduce the operating time delay of the relay. © 2014 by the authors; licensee MDPI, Basel, Switzerland.
Author supplied keywords
Cite
CITATION STYLE
Lee, B. E., Lee, J., Won, S. H., Lee, B., Crossley, P. A., & Kang, Y. C. (2014). Saturation detection-based blocking scheme for transformer differential protection. Energies, 7(7), 4571–4587. https://doi.org/10.3390/en7074571