Carbon dioxide: Making the right connection

0Citations
Citations of this article
13Readers
Mendeley users who have this article in their library.

Abstract

Carbon dioxide has been used in anaesthesia since the late 1920s, principally to stimulate breathing after a period of hyperventilation in the era before routine use of capnography. The authors’ tertiary academic hospital still has the infrastructure for pipeline delivery of carbon dioxide. A case is reported of accidental administration of carbon dioxide to a patient under anaesthesia, who was found to have end-tidal carbon dioxide (EtCO2) concentrations of greater than 25 kPa immediately after induction. This was confirmed on arterial blood-gas analysis. After successful resuscitation using an alternative oxygen source, it was discovered that the high concentrations were due to misconnection of gas pipelines during the refurbishment of a theatre. This highlights safety issues concerning pipeline provision of carbon dioxide, and that it is of utmost importance to confirm correct gas connections and supply before a new theatre is commissioned.

Cite

CITATION STYLE

APA

Gibbs, M. W., & Hofmeyr, R. (2017). Carbon dioxide: Making the right connection. Southern African Journal of Anaesthesia and Analgesia, 23(3), 76–78. https://doi.org/10.1080/22201181.2017.1332292