Abstract
To address the inability to monitor the performance status of Motor-Operated Valves (MOV) during the operation of nuclear power plants, develop the MOV status evaluation model and design a valve online monitoring system. During valve operation, the data acquisition unit (DAU) installed in the distribution cabinet of the motor control center (MCC) can capture the voltage, current and switch signals. On the basis of the aforementioned parameters, the active power curve and characteristic points of the valve can be determined, implemented monitoring and evaluation of the status and performance of MOV.
Cite
CITATION STYLE
Zhang, Y., Zhang, Y., Wang, P., Liu, B., & Wang, G. (2024). Monitoring and evaluation of the status of Motor-Operated Valves in nuclear power plants. In Journal of Physics: Conference Series (Vol. 2703). Institute of Physics. https://doi.org/10.1088/1742-6596/2703/1/012090