Transient stability analysis of grid-tied converters considering PLL’s nonlinearity

99Citations
Citations of this article
50Readers
Mendeley users who have this article in their library.
Get full text

Abstract

Transient instability events of grid-tied converters probably occur while riding through grid faults. During low-voltage ride through (LVRT) period, seeing from the converter terminal towards the grid, the Thévenin equivalent grid impedance becomes pretty significant, accordingly making the converter terminal voltage highly sensitive to the output current. Under such circumstances, it is challenging for the converter to resynchronize with the grid via a phase-locked loop (PLL). This paper develops a reduced-order nonlinear model to elaborate on the dynamic synchronization characteristic of the converters. By considering the impact of grid impedance and analysing spatial vector tracking relation, resynchronization principle of the converters during LVRT is revealed. Besides, the impacts of circuit parameters and controller parameters, including residual grid voltage, grid impedance, current references, and PLL parameters, on the transient stability of the converters are investigated. The results are verified by simulation and experimental results.

Cite

CITATION STYLE

APA

He, X., Geng, H., & Ma, S. (2019). Transient stability analysis of grid-tied converters considering PLL’s nonlinearity. CPSS Transactions on Power Electronics and Applications, 4(1), 40–49. https://doi.org/10.24295/CPSSTPEA.2019.00005